OVER HEAD DISTRIBUTION INSULATORS, STAY SETS & CRADLE GUARDS: Supply & erection of stay set consisiting of 19/20mm dia. 1.8 metre long G.I. stay rod duly threaded upto 300mm at one end and shped on the other end. MS plate size 30cm x 30cm x 6mm with 20mm dia. hole drilled in the centre of the plate G.I. stay wire size 7/10 SWG, G.I. thimble for stay, binding, Egg/Strain insulator, MS elbow made out of 16mm plain sheet and a piece of 50mm x 50mm x 6mm size 20cm long angle iron made to the shape as approved by Engineer-in-charge. Stay set complete shall be fixed to the pole by providing suitable size full clamps made out 50mm x 6mm size MS flat with required number of nut and bolts 16mm dia. on one end and shall be embedded in the on the other end. The stay plate shall be covered with cement concrete having total volume of the concrete not less that 0.042Cum. The job shall include excavation of pit and back filling and after pouring concrete with excavated soil etc. as approved/desired by the the Engineer-in-charge.